超特高壓變電站CVT二次全站一點(diǎn)接地隱患分析及改進(jìn)
	劉濤,湯會(huì)增,裴東良,喬振朋,王卓,王閃雷
	(國(guó)網(wǎng)河南省電力公司直流分公司,河南 鄭州 450051)
	 
	
		    摘 要:超特高壓變電站電容式電壓互感器(CVT)二次中性線不宜采用全站一點(diǎn)接地方式。以特高壓南陽(yáng)站為例,分析了全站一點(diǎn)接地方式下 CVT 自激法介損試驗(yàn)、繼電保護(hù)校驗(yàn)和 CVT 二次小間隙故障都會(huì)對(duì)全站 CVT 二次中性線共用回路產(chǎn)生影響,均可能導(dǎo)致運(yùn)行繼電保護(hù)裝置誤告警或誤動(dòng)作。提出 CVT 自激法介損試驗(yàn)使用反極性接入和執(zhí)行針對(duì)性的二次安全措施等防止運(yùn)行設(shè)備出現(xiàn)異常的方法,并給出基于CVT 二次拓?fù)鋱D和停電時(shí)序的二次回路改造方案,建議超特高壓變電站 CVT 二次中性線均獨(dú)立就地接地。
	
		    關(guān)鍵詞: 超特高壓變電站;電容式電壓互感器;一點(diǎn)接地;獨(dú)立接地
	
		    中圖分類號(hào):TM451+.2 ;TM63     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2025)09-0046-05
	
		 
	
		
			Analysis of Hidden Dangers and Improvement for Secondary Whole-Station
		
			One-Point Grounding of CVT in UHV/EHV Substation
		
			 
		
			
				LIU Tao, TANG Hui-zeng, PEI Dong-liang, QIAO Zhen-peng, WANG Zhuo, WANG Shan-lei
			
				(State Grid Henan DC Company, Zhengzhou 450051, China)
			
				 
			
				
					    Abstract: The secondary neutral line of capacitive voltage transformer (CVT) in UHV/EHV substation should not adopt substation-wide single-point grounding method. Taking the UHV Nanyang Substation as a case study, this study analyzes the impacts of CVT self-excitation dielectric loss testing, relay protection verification, and CVT secondary small-gap faults on the shared neutral line return circuit of CVT secondaries under the whole-station one-point grounding scheme. These factors may collectively induce false alarms or maloperation of in-service relay protection devices. To address these risks, this study proposes countermeasures to prevent operational abnormalities, including reverse-polarity connection during CVT self-excitation dielectric loss testing and implementation of targeted secondary safety measures.Additionally, a secondary circuit modification scheme is presented, based on CVT secondary topology diagrams and outage sequencing, recommending independent local grounding for the secondary line neutrals of UHV/EHV substation CVT.
				
					    Key words: UHV/EHV substation; capacitive voltage transformer; one-point grounding; independent grounding
				
					 
				
					
						參考文獻(xiàn)
					
						[1] 陳東明,王建偉,李旸,等. 電容式電壓互感器典型故障及缺陷分析[J] . 電力電容器與無(wú)功補(bǔ)償,2024,45(6) :36-43.
					
						[2] 胡嘯宇,吳杰,張晨晨,等. 一起 110 kV CVT 電壓異常的故障分析[J]. 電工電氣,2022(4) :72-73.
					
						[3] 張凱煜,沈云超,郭全軍,等. 一起 500 kV 電容式電壓互感器電壓異常事件的分析與處理[J] . 變壓器,2023,60(8) :65-70.
					
						[4] 趙彥林,周志新,何亮,等. 一起電容式電壓互感器二次電壓異常故障分析[J] . 電力電容器與無(wú)功補(bǔ)償,2025,46(1) :114-120.
					
						[5] 楊雪飛,楊紹遠(yuǎn),孫上元. 一起 500 kV 線路 CVT 故障原因分析及防范措施[J]. 電工電氣,2020(8) :73-74.
					
						[6] 史文玎,楊奇. 互感器二次回路施工驗(yàn)收常見(jiàn)問(wèn)題分析及防范[J]. 電工電氣,2024(1) :38-41.
					
						[7] 沙玉洲,萬(wàn)華,林浩凡,等. 某變電站操作合閘后電壓互感器燒毀的技術(shù)分析及改進(jìn)措施[J] . 變壓器,2024,61(11) :72-75.
					
						[8] 盛博聞. 電壓互感器二次回路多點(diǎn)接地的影響及查找措施[J]. 電力與能源,2024,45(4) :439-442.
					
						[9] 張春剛. 一起接地變零序電流保護(hù)動(dòng)作事件分析及預(yù)防[J]. 電工電氣,2023(12) :42-44.
					
						[10] 劉炬,劉闖,李俊,等. 一起中性點(diǎn)不接地系統(tǒng)線路送電時(shí)母線電壓異常分析[J] . 東北電力技術(shù),2025,46(4) :60-62.